Why an external motor for professional hoods — the golden rule
In commercial kitchen ventilation there is one simple rule: air laden with grease vapour must never pass through the fan motor.
With internal-motor fans, the air extracted from the hood passes through the motor to cool it. Grease builds up on the windings, the capacitor and the bearings. Under heavy use the motor fails within 1–2 years, and in extreme cases an electrical fire can start.
On the CF 0.5 HP 200 M4, the motor is completely separate from the extracted airstream. The impeller draws air from the hood and discharges it outside. The motor is cooled by room air through its own IP55 housing. There is no contact between the motor and the greasy kitchen air.
The smallest in the CF HP range — for small and medium kitchens
The CF 0.5 HP 200 M4 is the entry model of the CF HP range, for kitchens that do not need the higher airflow of the 250 or 300 mm models:
-
Bistros, cafés and pastry shops with hobs, ovens and small fryers
-
Pizzerias and fast-food outlets with a single cooking line
-
Guesthouse kitchens and small canteens
-
Confectionery and catering kitchens
As a guide: for medium-duty cooking (hobs, ovens, fryers), the airflow covers a wall hood of about 1.2–1.5 m, depending on duct length and grease filters. For longer hoods or heavy grilling, choose the CF 1 HP 250 M4.
The single-phase advantage
The 230 V motor connects to the venue’s standard electrical installation, with no three-phase supply. Speed is easily adjusted with a single-phase voltage controller. Airflow and noise adapt to demand: full speed at peak hours, reduced speed the rest of the time.
Built for hot, greasy air
-
Casing: galvanised steel sheet as standard; stainless steel on request for corrosive environments
-
Bucket-type impeller with sparse blades: grease does not build up between the blades, and cleaning is quick
-
Temperature: continuous operation from −20°C to +150°C
-
IE2 Simotop motor, to IEC 60034-30: lower energy use over long daily operating hours
-
Base with anti-vibration mounts: vibration is not transmitted to the hood or the building structure
Versions and complete units
-
CF 0.5 HP 200 M4 stainless steel: stainless casing for corrosive and humid environments
-
BOX HP acoustic plenum box: reduces noise in the dining room and neighbouring spaces
-
2,700 m³/h professional ventilation configurator: a complete unit, configured with ductwork, acoustic box and controller
Duct connection
The inlet is circular, Ø200 mm, and the outlet rectangular, 200 × 245 mm (internal). For a circular outlet duct, use a discharge reducer. Fit flexible connectors between the fan and the ductwork, and a backdraft grille at the outdoor discharge.
Dimensions (mm)
Technical specifications
-
Code: 05HP200M4EL
-
Type: single-inlet centrifugal, medium pressure, external motor
-
Nominal airflow: 2,700 m³/h
-
Motor: 0.37 kW, single-phase, 4-pole, IE2 (IEC 60034-30)
-
Power supply: 230 V / 50 Hz
-
Speed: 1,450 rpm
-
Rated current: 2.48 A
-
Protection: IP55
-
Insulation: Class F
-
Air temperature: −20°C … +150°C
-
Impeller: bucket type, sparse blades
-
Casing: galvanised steel sheet (stainless steel on request)
-
Inlet: Ø200 mm
-
Outlet: 200 × 245 mm
-
Dimensions (W × H × L): 460 × 480 × 500 mm
-
Speed control: by voltage or frequency
-
Mounting: on a base with anti-vibration mounts
👉 Stainless steel version
👉 BOX HP acoustic box
👉 2,700 m³/h professional ventilation configurator