A compact fan for casings, AHUs and hoods
The BD 9/9 M4 is the fan that equipment manufacturers fit into ventilation boxes, air handling units (AHU), air heaters and professional kitchen hoods. The double-inlet impeller gives it high airflow for its size. The single-phase supply means it connects to 230 V, with no three-phase panel. It fits in a space of about 38 × 41 × 36 cm.
How it works: suction on both sides
The impeller is open on both sides and draws in air from the left and right at the same time. With the same diameter, it moves much more air than a single-inlet impeller. The small forward-curved blades run at a low speed of 1,375 rpm. Airflow stays steady and noise stays low.
The motor sits directly in the impeller hub: no belts, no pulleys, no periodic re-tensioning. Motor and impeller are mounted on flexible silent-block arms, which stop vibration from reaching the casing and the building.
Performance
- Maximum airflow: 2,820 m³/h, at about 100 Pa
What this means in practice: the curve is flat between 1,000 and 2,000 m³/h. On a system with a filter, a coil and medium-length ductwork, the fan delivers about 2,000 m³/h, and if system resistance rises a little, airflow drops only slightly. That is why it is widely used in air heaters and AHUs with filters.
Construction
- Casing: galvanised steel sheet, corrosion-resistant
- Impeller: PA6 polyamide reinforced with glass fibre, light and balanced
- Motor: closed, extruded aluminium housing, IP54; terminal box IP65; Class F insulation; efficiency 71.8%; power factor 0.98
- Suspension: anti-vibration flexible arms
- Mounting feet: included in the price
- On request: galvanised steel impeller and factory-fitted outlet flange
Where you can use it
In professional kitchen hoods. It mounts in the hood body or above it, after the grease filters, for extraction or supply. Suitable for bistros, cafés, pastry shops and small kitchens.
In air handling units and heat recovery units. The compact size allows smaller casings, and the single-phase supply simplifies the controls.
In air heaters and fresh air units. With a filter and a hot water heating coil, it supplies heated fresh air to workshops, shops and sports halls.
In ventilation boxes and false ceilings. It extracts or supplies air in offices, shops, salons and restaurants.
When it is NOT suitable
- Hot, greasy air above 50 °C, for example over heavy grills: choose a Casals CF HP kitchen hood fan with an external motor, designed for air up to 150 °C.
- Airflow above 3,000 m³/h: choose the DD 9/9 M96R, 3,990 m³/h and also single-phase 230 V, or the OMNIBOX DD 10/10 configurator, 7,000 m³/h.
Installation and wiring
The single-phase motor connects to L and N, and the 18 µF capacitor is included in the wiring. To control airflow and noise, use a single-phase voltage controller rated at least 3 A. For maintenance, fit a safety isolator switch next to the fan.
Dimensions (mm)
- Overall length (I): 376
- Overall height (G): 407
- Casing width (A): 301
- Maximum width, with motor (B): 354.5
- Foot spacing (C × D): 330 × 245
- Shaft height (H): 191
- Inlet internal diameter (X): 202
Technical specifications
- Type: double-inlet centrifugal, forward-curved blades, direct drive
- Maximum airflow: 2,820 m³/h
- Maximum static pressure: approx. 355 Pa
- Motor: 0.35 kW, single-phase, 4-pole, STC80
- Power supply: 230 V / 50 Hz
- Speed: 1,375 rpm
- Maximum current: 2.83 A
- Capacitor: 18 µF / 400 V
- Motor efficiency: 71.8%
- Power factor: 0.98
- Protection: motor IP54, terminal box IP65
- Insulation: Class F
- Maximum air temperature: 50 °C
- Impeller: PA6 polyamide reinforced with glass fibre
- Casing: galvanised steel sheet
- Dimensions (L × H × W): 376 × 407 × 354.5 mm
- Weight: 12 kg
- Speed control: single-phase voltage controller
- Mounting feet: included
👉 More powerful version, DD 9/9 M96R, 3,990 m³/h
👉 OMNIBOX DD 10/10 configurator
📞 +40 722 667 238 — free consultancy