Welcome to our store!
Home Fans Smoke extract fans Outside the hazardous area 600 C/2h Smoke extract wall fan - RWM 57-3540-6W-10

Smoke extract wall fan - RWM 57-3540-6W-10

Price excl. tax: €4.57551
Price inc. tax: €5.53637

Pre-order

Wall-mounted smoke extract fan rated 600°C/120 min, 6-pole IE2 motor, 925 RPM — the low-noise variant on the Ø395mm casing.

Maximum airflow ~3,500 m³/h, ~240 Pa, 0.37 kW / 400V three-phase, 61 kg, 74 dB(A).

Lower consumption and noise than the 4-pole model on the same casing — the correct choice when moderate airflows and acoustic limits take priority.

Certified DIN EN 12101-3, No. 0036-CPR-RG01-17.

  • Air flow:
    3390 m3/h
  • Motor type:
    AC motor
  • Motor power:
    0.37 kW
  • Voltage:
    230/400 V - 50 Hz
  • Motor speed:
    4 POLE
Add to wishlist

Quick Buy

Just 4 fields to fill in
We will contact you to finalize the order
  • RWM5735406W10
  • 61.000 Kgs

The 6-pole motor version (925 RPM) on the Ø395mm casing — the same housing as the RWM 57-3540-4W-10, but with lower speed, reduced power consumption (0.37 kW vs 0.55 kW) and a sound power level 10 dB(A) lower (74 vs 84 dB(A)). The correct choice when regulations or the client impose acoustic limits and an airflow of 3,500 m³/h is sufficient for the designed smoke extraction system.

 

The Nicotra Gebhardt RWM 57 series comprises wall-mounted fans for smoke extraction in the event of fire, certified for operation at 600°C for 120 minutes — the highest fire resistance class in standard DIN EN 12101-3. This certification exceeds the standard F400 class and is mandatory in road tunnels, railway tunnels and buildings with extreme fire risk.

The essential construction feature: the motor is positioned completely outside the hot gas zone and cooled by outside air — the only solution that allows operation at 600°C without motor damage.

Construction: robust galvanised steel casing · galvanised steel intake cone with DIN 24155-2 flange connection · backward curved welded coated steel impeller · all mechanically stressed parts in galvanised or painted steel · IE2 motor completely outside the gas flow · loose feed cable to motor connection box.

All models are certified to DIN EN 12101-3, with horizontal discharge, RD rotation, standard handing 90.

  • Air flow:
    3390 m3/h
  • Motor type:
    AC motor
  • Motor power:
    0.37
    kW
  • Voltage:
    230/400 V - 50 Hz
  • Motor speed:
    4 POLE
  • Mounting:
    On wall

Duct pressure drop calculator

💨 Calculator pierderi de presiune în tubulaturi

Chat WhatsApp
Cu ce te putem ajuta astazi?