Welcome to our store!
Home Fans Smoke extract fans Impuls JET fans JET fans - JF 300 T2 UN CONFORT

JET fans - JF 300 T2 UN CONFORT

Price excl. tax: €2.75700
Price inc. tax: €3.33597

Pre-order

Casals JF 300 T2 UN CONFORT — unidirectional axial jet fan designed for polluted air (CO, CO₂) and accidental fire smoke evacuation in underground car parks and large spaces, in compliance with normative NP 24-2022.

Maximum airflow 4,500 m³/h, thrust force 26 N, three-phase motor 0.55 kW, 2,780 rpm, current 1.36A / 400V, protection IP55, insulation Class F, maximum operating temperature 60°C.

Composed of an axial fan with galvanised steel casing flanked by 2 mineral wool silencers — significant acoustic attenuation versus non-silenced jet fans.

The UN (unidirectional) variant is equipped with an inlet protection guard and an outlet deflector that directs the air jet away from the ceiling and obstacles, sweeping the complete air volume towards the extraction point.

Total length: 2,415 mm. Weight: 60 kg

  • Air flow:
    4500 m3/h
  • Motor type:
    AC motor
  • Motor power:
    0.55 kW
  • Voltage:
    230/400 V - 50 Hz
  • Motor speed:
    2 POLE
Add to wishlist

Quick Buy

Just 4 fields to fill in
We will contact you to finalize the order
  • 274300196ST
  • 60.000 Kgs

AXIAL JET FAN CONFORT

MANUFACTURING FEATURES:

The JF models are composed of an axial fan and two silencers.

FAN:
• Axial fan with galvanized steel casing. The connection box is accessible by the side from a removable door.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation,  Standard voltages 230/400V 50Hz for 1 speed motors and 400V 50Hz for 2 speed motors.

SILENCERS:
• Casing in galvanized steel. Inner duct made of perforated galvanized steel sheet. The silencers are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.
• Unidirectional JF CONFORT UN is equipped with a protection guard at the inlet side and a deflector at the outlet. The deflector directs the air away from the ceiling and obstacles like beams or ducting, sweeping the whole volume of air to the closest extraction point.

APPLICATIONS:

• Conceived for car parkings and large spaces where polluted air, or smoke from an accidental fire, needs to be removed effectively. An optimized design minimizes the height needed for their installation and assures a silent operation.
• Maximum working temperature: 60ºC.

 

FULL TECHNICAL SPECIFICATIONS EN:

Specification Value
Model code 274300196ST
Type Unidirectional axial jet fan with silencers
Application Underground car parks, large spaces — CO and smoke extraction
Maximum airflow 4,500 m³/h
Thrust force 26 N
Speed 2,780 rpm
Motor power 0.55 kW
Max. current 400V 1.36A
Voltage 230/400V or 400/690V / 50Hz
Speeds 1
Motor protection IP55
Insulation class F (155°C)
Max. operating temperature 60°C
Silencers 2× mineral wool
Deflector Yes (directs jet away from ceiling)
Inlet guard Yes
Total length (A) 2,415 mm
Total height with supports (B) 590 mm
Casing diameter (G) 334 mm
Total weight 60 kg
Motor weight 12 kg
Applicable normative NP 24-2022

 

  • Air flow:
    4500 m3/h
  • Suction size:
    300 mm
  • Motor type:
    AC motor
  • Motor power:
    0.55
    kW
  • Voltage:
    230/400 V - 50 Hz
  • Motor speed:
    2 POLE
File Info
JF-300-T2-UN-CONFORT [PDF, 395.04 KB]
iso_casals_en [PNG, 274.36 KB]

Duct pressure drop calculator