Industrial-hall airflow from a compact fan
The DDM 12/12 M7A2 moves almost 12,000 m³/h through a casing of only 490 × 521 × 451 mm. On a system with a filter, a heating coil and ductwork, it keeps around 9,000–10,000 m³/h. It is the right fan for:
-
high-airflow air handling units
-
air heaters and heated fresh air units for industrial halls
-
ventilation boxes for commercial and industrial spaces
The double-inlet impeller draws air from both sides at once. This gives it an airflow that a single-inlet fan reaches only with a much larger casing.
Measured performance
Manufacturer’s curve at maximum speed (400 V, delta connection):
-
0 Pa, free discharge: approx. 12,000 m³/h
-
200 Pa: approx. 10,000 m³/h
-
400 Pa: approx. 8,800 m³/h
-
600 Pa: approx. 7,500 m³/h
-
Maximum static pressure: approx. 700 Pa
On a typical installation (filter, heating coil, medium-length ductwork, 200–400 Pa), the fan delivers 9,000–10,000 m³/h. At high resistance, airflow drops gradually, not suddenly.
Note: the manufacturer advises against operating the fan in the area to the left of the curve (below about 5,000 m³/h at full speed), where operation becomes unstable. If you need less airflow, reduce the speed.
Noise: sound power level LWA is 85–95 dB, depending on the operating point. For occupied spaces, install it in an acoustic box and use duct silencers.
Two speeds, by connection
The three-phase motor has two speeds:
-
Delta (Δ): maximum speed, up to ~12,000 m³/h
-
Star (Y): reduced speed, about 8,000 m³/h at free discharge, with lower noise and energy use
For continuous control, the manufacturer allows a transformer, a TRIAC controller or a frequency inverter. Size the controller for the motor’s maximum current of 9.7 A.
Construction
-
Casing: galvanised steel sheet, seamed
-
Impeller: galvanised steel, forward-curved blades, dynamically balanced to ISO 1940
-
Motor: 2.2 kW, IP54, Class F, external thermal protection (thermal contacts at the terminal box)
-
Discharge flange: factory-fitted
-
Installation type (ISO 5801): B, meaning free inlet and ducted outlet
-
Casing, impeller and motor are all made by Nicotra Gebhardt
Where you can use it
Heated fresh air for industrial halls. With a BAC 120 (120 kW, 11,000 m³/h) or BAC 90 hot water heating coil and a G4 filter, you build a fresh air unit for workshops, warehouses and sports halls of 1,000–2,000 m².
High-airflow air handling units and heat recovery units for offices, shops, hotels and event halls.
Acoustic ventilation boxes, such as the BOX PLUS 12/12, for ducted extraction or supply.
General industrial ventilation: production halls, warehouses, large commercial spaces.
When it is NOT suitable
-
Hot, greasy air above 40 °C, such as from kitchen hoods: choose a CF HP fan with an external motor, designed for air up to 150 °C.
-
Low airflow, below 5,000 m³/h: choose a smaller model, such as the DD 9/9 M96R (3,990 m³/h, single-phase) or the OMNIBOX DD 10/10 (7,000 m³/h).
Recommended installation
-
On the discharge: a gravity backdraft grille, sized to the flange
-
Between the fan and the ductwork: flexible anti-vibration connectors
-
Next to the fan: a maintenance isolator switch, e.g. EME5-20-4111
-
On the inlet: a G4 filter, if air is drawn from outside
-
To balance the system: a damper in the ductwork
Dimensions (mm)
Technical specifications
-
Type: double-inlet centrifugal (DWDI), forward-curved blades, direct drive
-
Maximum airflow: approx. 11,000 m³/h
-
Airflow at 200 Pa: approx. 10,000 m³/h
-
Airflow at 400 Pa: approx. 8,800 m³/h
-
Maximum static pressure: approx. 700 Pa
-
Motor: 2.2 kW, three-phase, 4-pole
-
Power supply: 400 V / 50 Hz
-
Connection: Δ/Y, 2 speeds
-
Speed: 1,400 rpm
-
Maximum current: 9.7 A
-
Maximum power consumption: 5,780 W
-
Speed control: transformer, TRIAC or frequency inverter
-
Protection: IP54
-
Insulation: Class F, external thermal protection
-
Maximum air temperature: 40 °C
-
Noise (sound power LWA): 85–95 dB, depending on the operating point
-
Casing and impeller: galvanised steel, balanced to ISO 1940
-
Dimensions (L × H × W): 490.5 × 521 × 451 mm
-
Weight: 59 kg
-
Supplied with: fitted discharge flange
-
Testing: AMCA 210 / ISO 5801, installation type B